Used Fulton VSRT Vertical Steam Boilers for Sale
Used Fulton VSRT Vertical Steam Boilers
VSRT stands for Vertical Spiral Rib Tubeless. It is Fulton’s vertical steam boiler line, built in Pulaski, New York, and sold in sizes from 9.5 to 250 boiler horsepower. The number after VSRT is the horsepower, so a VSRT-30 (often written VSRT 30 or VSRT30) is a 30 HP steam boiler.
Boilers.com buys and sells used commercial and industrial boilers and ships nationwide from Miami, Florida. Here is a plain explanation of how a VSRT is built, Fulton’s published ratings for each size, the used VSRT units we have listed, and what to check before you buy one.
What makes a VSRT different
Fulton has built vertical tubeless steam boilers since 1949. A tubeless boiler has no fire tubes to plug, leak, or replace. The VSRT keeps that idea and adds a spiral rib heat exchanger, which Fulton says gives the hot gases a long heat transfer path in a small space.
- Fully wetted pressure vessel. The vessel is water backed and wrapped in high-density insulation. There is no refractory to crack or reline.
- No retubing. Fulton lists “never needs re-tubing” as a standard feature, because there are no tubes.
- Thick walls. Fulton specifies a 0.375 inch minimum wall. Both used VSRT units we list have 3/8 inch shells and 1.25 inch heads on the nameplate.
- Efficiency and emissions. Fulton publishes operating efficiencies up to 86 percent and NOx below 20 ppm as standard.
- Burner. A fully modulating burner with a variable speed combustion air blower. Turndown runs from 4:1 to 10:1 depending on size.
- Pressure. 150 PSIG maximum allowable working pressure, and the boiler can be trimmed to operate from 15 to 150 PSIG.
- Fuel. Natural gas, propane, or dual fuel. Both VSRT units in our inventory are natural gas.
- Small footprint. A VSRT-20 or VSRT-30 is about 33 inches wide without trim, which suits tight mechanical rooms.
Fulton VSRT ratings by size
The figures below are from Fulton’s current VSRT specification table, for natural gas. Steam output is from and at 212°F. Older units can differ slightly from current literature, so a used boiler’s nameplate is the authority for that specific unit.
Key specs at a glance
Published VSRT facts from Fulton’s specification table and product description. Confirm every figure on the nameplate of the unit you buy.
| Model | Fuel input (Btu/hr) | Output (Btu/hr) | Steam output (lbs/hr) | Turndown |
|---|---|---|---|---|
| VSRT-9.5 | 385,000 | 318,000 | 328 | 8:1 |
| VSRT-10 | 400,000 | 335,000 | 345 | 4:1 |
| VSRT-15 | 600,000 | 503,000 | 518 | 6:1 |
| VSRT-20 | 800,000 | 670,000 | 690 | 4:1 |
| VSRT-30 | 1,200,000 | 1,005,000 | 1,035 | 6:1 |
| VSRT-40 | 1,600,000 | 1,340,000 | 1,380 | 6:1 |
| VSRT-50 | 1,993,000 | 1,674,000 | 1,725 | 8:1 |
| VSRT-60 | 2,392,000 | 2,008,000 | 2,070 | 10:1 |
| VSRT-80 | 3,200,000 | 2,678,000 | 2,760 | 10:1 |
| VSRT-100 | 4,000,000 | 3,348,000 | 3,450 | 10:1 |
| VSRT-125 | 4,990,000 | 4,185,000 | 4,313 | 10:1 |
| VSRT-250 | 9,800,000 | 8,370,000 | 8,625 | 10:1 |
One boiler horsepower is the equivalent evaporation of 34.5 pounds of water per hour from and at 212°F. That is why a VSRT-30 is rated 1,035 lbs/hr (30 × 34.5) and a VSRT-20 is rated 690 lbs/hr (20 × 34.5).
Used Fulton VSRT boilers in stock
We currently list two used VSRT steam boilers. Inventory changes, so check our used boilers inventory or call us for the latest.
A 2017 Fulton VSRT 30 (yard tag BSF30HP39). It is a 30 HP steam boiler rated 150 PSI, fired on natural gas. The nameplate rating is 1,035 lbs/hr of steam and 1,005,000 Btu/hr output, with a maximum input of 1,200,000 Btu/hr. It has a stainless steel shell, a Fulton VSRT control panel, a cyclone combustion air separator, and a burner and blower assembly with a variable frequency drive. The boiler is rated 240V single phase.
A 2018 Fulton VSRT 20 (yard tag BSF20HP228), located in Massachusetts. It is a 20 HP steam boiler rated 150 PSI, fired on natural gas, with 690 lbs/hr of steam and 670,000 Btu/hr output on the nameplate, and National Board No. 228. It is skid mounted and rated 120V single phase. The sale includes a Fulton feedwater and condensate return tank system and a Fulton blowdown separator, so it is a good start on a complete small steam plant.
If you need a different Fulton vertical, the FB-010-A and VMP-130 above are older Fulton designs, not VSRTs. The 2023 Fulton Classic FB-010-A is a 10 HP, 150 PSI natural gas vertical tubeless steam boiler. The Fulton VMP-130 is a 130 HP, 150 PSI packaged vertical steam boiler rated 4,485 lbs/hr.
Typical uses for a Fulton VSRT
A VSRT is a small to mid-size steam boiler for plants that need dry steam without a large boiler room. Fulton markets it for process manufacturing, food and beverage processing, healthcare, pharmaceutical and biotech, education, government and military, agriculture, utilities, and commercial buildings. Fulton also says the tall steam space gives steam quality of 99.75 percent or better, which matters for sterilizers, humidification, and direct-contact process steam.
What to check when buying a used VSRT
The VSRT design removes the two big repair items on a typical firetube, tubes and refractory. That does not make every used unit a safe buy. Inspect the boiler in person, or have a qualified inspector do it, and match every claim to the nameplate and the records.
We can help arrange an inspection and quote freight and rigging anywhere in the country.
FAQ
What does VSRT stand for?
Vertical Spiral Rib Tubeless. It is Fulton’s vertical steam boiler with a spiral rib heat exchanger and a fully wetted, refractory-free pressure vessel.
How much steam does a Fulton VSRT make?
From 328 lbs/hr for a VSRT-9.5 up to 8,625 lbs/hr for a VSRT-250, from and at 212°F. A VSRT-20 is rated 690 lbs/hr and a VSRT-30 is rated 1,035 lbs/hr. Actual output in your plant depends on feedwater temperature, operating pressure, and the boiler’s condition.
Is a VSRT a firetube boiler?
It is a vertical tubeless boiler. The hot gases pass along the spiral rib heat exchanger inside a water-backed vessel rather than through a bundle of fire tubes. Our listings file it under firetube, since it is not a watertube design.
Does a VSRT need retubing?
No. There are no tubes, and Fulton lists “never needs re-tubing” as a standard feature. You still need to keep up water treatment, blowdown, and burner service.
What fuels can a VSRT burn?
Fulton offers natural gas, propane, and dual fuel. Both used VSRT units we have listed are natural gas. Check the nameplate and fuel train on any used unit.
How do I get pricing or schedule a look at a unit?
Call (305) 428-2777 or use our contact page. Tell us the steam load, pressure, fuel, voltage, and timing you need. We will confirm what is in stock, send specs and availability, and help with inspection and nationwide shipping. If you have a Fulton to sell, see we buy boilers.
Look at a used Fulton VSRT, or tell us what you need
If a compact vertical steam boiler is the right fit, start with the 2017 VSRT 30 or the 2018 VSRT 20 with feedwater system, or browse all used boilers. Need steam right away? Ask about our boiler rentals. For a quote or help sizing a VSRT for your plant, contact us or call (305) 428-2777. We serve plants nationwide from Miami, Florida.